Cold Room Not Cooling Properly? 10 Possible Causes

Industrial blast freezer compressor installation by Glotech Group in Hermanus

A cold room that is running but not reaching its set temperature should be investigated promptly.

The problem may be relatively simple, such as a blocked condenser or damaged door seal. It may also indicate a more serious refrigeration fault involving refrigerant loss, failed fans, incorrect defrost operation or compressor damage.

Common warning signs include:

  • The room temperature remains above the controller setpoint
  • The compressor runs for unusually long periods
  • The temperature rises after every delivery and recovers slowly
  • Some parts of the room are cold while others remain warm
  • Ice builds up on the evaporator
  • The condenser repeatedly trips on high pressure
  • Products near the door feel warmer than those at the back
  • The displayed temperature differs from the product temperature
  • Electricity consumption increases unexpectedly
  • The room no longer performs during hot weather

Cold-room faults commonly fall into categories involving temperature control, compressor operation, evaporator icing, condenser pressure, refrigerant feed and system capacity. A structured diagnosis is important because several different faults can produce the same symptom.

This guide explains ten possible reasons why a commercial cold room may not be cooling properly, what signs to look for and when professional refrigeration repairs are required.

First Confirm That the Cold Room Is Actually Too Warm

Before assuming that the refrigeration system has failed, confirm the temperature accurately.

The controller display normally shows the temperature at the position of its sensor. That reading may not represent the temperature of every product inside the room.

Check:

  • The controller setpoint
  • The temperature displayed
  • An independent calibrated thermometer
  • Product temperature where appropriate
  • Whether the door was recently open
  • Whether warm stock was recently loaded
  • Whether the system is currently defrosting
  • Whether the fans are running
  • Whether the compressor is operating

Allow for the normal control differential. For example, a controller set at +3°C may switch the compressor on and off across a small temperature range rather than holding exactly +3°C at every moment.

A temperature that continues rising or remains significantly above the intended range requires further investigation.

1. Dirty or Blocked Condenser Coil

The condenser removes heat from the refrigerant and releases it into the surrounding air.

When the condenser coil becomes covered with dust, grease, lint or other debris, heat cannot escape efficiently. Condensing pressure rises, the compressor works harder and cooling capacity can fall.

Danfoss identifies dirty or clogged condenser surfaces as a cause of excessive condensing pressure and refrigeration-system problems. It also lists poor ventilation and excessive system load among causes of high head pressure.

Common signs of a dirty condenser

  • Compressor running for long periods
  • Condensing unit unusually hot
  • High-pressure trips
  • Reduced cooling during hot weather
  • Increased electricity use
  • Dust or grease visible on the coil
  • Condenser fan blowing very hot air
  • Room temperature recovering slowly

Commercial kitchen condensers are particularly vulnerable because airborne grease can stick to the coil and trap dust.

What should be done?

The condenser should be cleaned using a method suitable for the equipment and contamination.

This may involve:

  • Isolating electrical power
  • Removing loose dust
  • Cleaning between coil fins
  • Straightening damaged fins where appropriate
  • Removing grease with an approved coil cleaner
  • Confirming that ventilation openings are clear

High-pressure water should not be directed at delicate coil fins or electrical components.

A repeatedly dirty condenser usually indicates that the maintenance interval is too long or that the unit is installed in a contaminated environment.

2. Refrigerant Leak or Insufficient Refrigerant Charge

Refrigerant absorbs heat inside the cold room and carries it to the condenser.

If refrigerant escapes through a leak, the system may continue running but lose cooling capacity. The room temperature can gradually rise even though the compressor appears to be operating normally.

Possible leak locations include:

  • Copper pipe joints
  • Flare connections
  • Brazed connections
  • Schrader valves
  • Service ports
  • Evaporator coils
  • Condenser coils
  • Receiver connections
  • Pressure controls
  • Vibration-damaged pipework
  • Corroded tubing

Copeland recommends routine leak inspections because one visible leak may not be the only leak in the refrigeration system.

Possible signs of refrigerant loss

  • Compressor runs continuously
  • Room no longer reaches the setpoint
  • Only part of the evaporator becomes cold
  • Ice forms in one limited section of the coil
  • Bubbles appear in a liquid-line sight glass where fitted and applicable
  • Oil stains appear around joints
  • Suction pressure is lower than expected
  • The compressor becomes unusually hot
  • Cooling performance gradually worsens
  • The system has required repeated regassing

Why regassing alone is not enough

Refrigerant is not normally consumed during system operation. If the charge is low, there is usually a leak or previous servicing issue.

Adding refrigerant without finding and repairing the leak may provide only temporary improvement.

A proper repair may include:

  1. Locating the leak
  2. Recovering refrigerant where necessary
  3. Repairing or replacing the leaking component
  4. Pressure testing the system
  5. Evacuating air and moisture
  6. Recharging by the correct method
  7. Confirming pressures, superheat or subcooling as applicable
  8. Testing room-temperature performance

Refrigerant work should be performed by a qualified commercial refrigeration technician.

3. Failed Condenser Fan

The condenser fan pulls or pushes air across the condenser coil so that heat can be rejected.

If the fan stops, the coil may remain extremely hot. Condensing pressure can rise rapidly, potentially causing the high-pressure safety control to stop the compressor.

Danfoss identifies stopped condenser fans, failed fan motors and inadequate condenser ventilation as causes of excessive head pressure.

Signs of a failed condenser fan

  • Compressor runs but condenser fan does not
  • Condensing unit becomes excessively hot
  • System stops on high pressure
  • Fan starts intermittently
  • Fan rotates slowly
  • Unusual fan noise
  • Burnt smell from the motor
  • Fan blade is damaged
  • Motor is hot but not turning
  • Cooling fails mainly during warm weather

Possible causes include:

  • Failed fan motor
  • Damaged capacitor
  • Loose electrical connection
  • Failed contactor
  • Tripped overload
  • Broken fan blade
  • Incorrect controller signal
  • Obstruction preventing movement

The unit should not be allowed to run repeatedly under excessive condenser pressure, as this can place additional strain on the compressor.

4. Evaporator Coil Iced Up

The evaporator absorbs heat from the cold-room air.

A light frost pattern may be normal in some systems, but a coil covered by a thick block of ice cannot move enough air or transfer heat efficiently.

Heatcraft troubleshooting guidance instructs technicians to check for an iced evaporator and inspect the defrost cycle, sensor and control parameters.

Signs of an iced evaporator

  • Thick frost or solid ice on the coil
  • Little or no air coming from the fans
  • Fans striking ice
  • Uneven room temperature
  • Compressor runs continuously
  • Room initially cools, then becomes warmer
  • Water appears after ice melts
  • Ice forms around the drain pan or fan guards

Possible causes of evaporator icing

  • Failed defrost heater
  • Incorrect defrost schedule
  • Failed defrost sensor
  • Defrost ending too early
  • Evaporator fans running during the wrong part of defrost
  • Blocked or frozen drain
  • Door left open
  • Damaged door gasket
  • Excessive moisture entering the room
  • Refrigerant underfeeding
  • Failed evaporator fan
  • Incorrect controller settings

Heatcraft notes that a coil may fail to clear when defrost heat is insufficient or the coil does not reach the required temperature during defrost.

Should you break the ice off manually?

Do not strike the evaporator with knives, screwdrivers or other sharp tools.

The tubing and fins can be damaged, causing a refrigerant leak or costly coil replacement.

The coil should be safely defrosted, and the cause of the ice build-up must then be corrected. Simply melting the ice without repairing the defrost, airflow or door problem will usually result in the fault returning.

5. Damaged or Poorly Sealing Door Gasket

A damaged cold-room door seal allows warm, humid air to enter continuously.

This increases the refrigeration load and can lead to:

  • High room temperature
  • Condensation around the doorway
  • Ice on freezer-room doors
  • Evaporator icing
  • Long compressor cycles
  • Water on the floor
  • Increased electricity consumption

Signs of a door-seal problem

  • Visible tears or gaps in the gasket
  • Door does not close evenly
  • Light visible through the frame
  • Condensation around the opening
  • Ice along the door edge
  • Door requires lifting to close
  • Damaged hinges or sliding-door rollers
  • Warm air can be felt entering
  • Gasket has hardened or pulled away

The gasket may not be the only issue. The door can also leak because of:

  • Misaligned hinges
  • Worn rollers
  • Damaged frame
  • Uneven floor
  • Loose latch
  • Bent door leaf
  • Damaged threshold
  • Incorrect pressure relief in a freezer room

A simple paper test can identify some obvious gaps: close the door on a strip of paper and check whether it is held firmly at different points around the frame. This does not replace a complete door assessment.

6. Incorrect Temperature-Controller Setting or Sensor Fault

The refrigeration equipment may be operating correctly but responding to an incorrect setpoint, differential, sensor reading or control programme.

Possible controller problems include:

  • Setpoint accidentally changed
  • Differential set too wide
  • Controller in standby mode
  • Incorrect temperature units
  • Probe offset entered incorrectly
  • Defrost scheduled too frequently
  • Defrost lasting too long
  • Fans programmed incorrectly
  • Sensor positioned in an unsuitable location
  • Sensor damaged or disconnected
  • Controller relay failure

Signs of a controller problem

  • Displayed temperature does not match an independent thermometer
  • Compressor switches off while the room is still warm
  • Controller shows an alarm code
  • System remains in defrost
  • Fans do not restart after defrost
  • Setpoint has changed unexpectedly
  • Temperature fluctuates in a repeated pattern
  • Controller display is blank or unstable

Do not change multiple controller parameters without recording the original settings.

Incorrect changes can create additional faults, especially in freezer systems where defrost termination, fan delay and compressor protection must work together.

7. Compressor Problems

The compressor circulates refrigerant through the system and creates the pressure difference required for refrigeration.

A compressor can be heard running but still fail to pump effectively.

Copeland explains that a compressor’s role is to raise refrigerant vapour pressure so that heat can be rejected through the condenser.

Possible compressor faults

  • Worn internal valves
  • Scroll damage
  • Motor winding damage
  • Internal overload operation
  • Loss of pumping capacity
  • Incorrect rotation on a three-phase compressor
  • Low supply voltage
  • Phase loss
  • High discharge temperature
  • Oil-management problems
  • Refrigerant floodback
  • Liquid slugging
  • Repeated overheating

Signs of compressor trouble

  • Compressor runs but suction and discharge pressures remain too similar
  • Compressor is unusually noisy
  • Unit trips the circuit breaker
  • Internal overload repeatedly opens
  • Compressor starts and stops rapidly
  • Shell temperature is excessive
  • Motor draws abnormal current
  • Cooling capacity has declined despite clean coils and correct airflow
  • Compressor hums but does not start
  • Oil is discoloured or contaminated

A compressor should not be replaced until the cause of the failure is identified.

Installing a new compressor without correcting problems such as poor condenser ventilation, refrigerant undercharge, liquid floodback or incorrect electrical supply can lead to another failure.

Electrical testing and compressor diagnosis should be performed by a trained technician because refrigeration systems contain high pressures, high starting currents and potentially hazardous refrigerants.

8. Poor Airflow Inside the Cold Room

A cold room can reach the correct temperature near the sensor while products elsewhere remain too warm.

This often happens when cold air cannot circulate around the stock.

Causes of poor airflow

  • Products stacked against the evaporator
  • Return-air path blocked
  • Boxes stacked against walls
  • Stock packed tightly to the ceiling
  • Evaporator fan failure
  • Ice on the evaporator
  • Incorrect shelving layout
  • Overloaded room
  • Damaged fan blade
  • Incorrect evaporator position
  • Plastic wrapping obstructing air passages

Signs of poor airflow

  • Warm areas inside the room
  • Products near the evaporator are cold but distant products are warm
  • Limited air movement
  • Large difference between probe and product temperatures
  • Ice forms in particular areas
  • Evaporator fans sound abnormal
  • Temperature improves after stock is rearranged

How stock should be arranged

Leave sufficient space for:

  • Air leaving the evaporator
  • Air returning to the evaporator
  • Circulation between product stacks
  • Clearance above the highest stock
  • Cleaning around walls and floors
  • Access to the evaporator for servicing

Do not use every cubic metre of the room as product space.

Airflow is part of the storage system. A heavily overstocked room may have enough refrigeration capacity under design conditions but still fail to maintain uniform product temperature.

9. Insulation or Panel Failure

The refrigeration system removes heat, while the insulated enclosure limits the amount of heat entering.

If wall, ceiling, floor or door insulation is damaged, the refrigeration equipment may no longer keep up with the additional heat load.

Possible insulation problems

  • Open panel joints
  • Damaged panel skins
  • Wet insulation
  • Poorly sealed corners
  • Unsealed pipe penetrations
  • Missing floor insulation
  • Damaged ceiling panels
  • Thermal bridges
  • Deteriorated sealant
  • Gaps around the door frame
  • Panels unsuitable for the required temperature

Signs of enclosure failure

  • Condensation on external panel surfaces
  • Water or ice around joints
  • Soft or swollen panels
  • Corrosion near panel seams
  • Mould around corners
  • Localised warm areas
  • Compressor runs continuously
  • Room struggles mainly during hot weather
  • Electricity consumption rises over time

Moisture entering the insulation can reduce thermal performance and cause progressive deterioration.

Panel failure is particularly serious in freezer rooms because water inside joints or insulation may freeze and expand.

How insulation faults are assessed

A technician or panel specialist may use:

  • Visual inspection
  • Surface-temperature readings
  • Thermal imaging
  • Joint inspection
  • Moisture assessment
  • Door alignment checks
  • Review of panel thickness and core material
  • Comparison of internal and external temperatures

Repair may involve resealing joints, replacing damaged panels, correcting penetrations, repairing the floor or rebuilding part of the enclosure.

10. Refrigeration Unit Is Undersized

A cold room may have no failed components but still be unable to maintain temperature because the refrigeration plant is too small for the actual load.

Danfoss recommends confirming that system and component capacity match the required load when troubleshooting a walk-in cooler or freezer.

Why a system becomes undersized

The room may have been incorrectly designed from the beginning, or operating conditions may have changed.

Possible causes include:

  • Room enlarged without upgrading refrigeration
  • More stock loaded each day
  • Products now enter at a warmer temperature
  • Door opened more frequently
  • Business operating hours extended
  • Higher ambient temperature
  • Additional lighting or equipment installed
  • Condenser moved into a poorly ventilated area
  • Target temperature reduced
  • Cold room changed to a different product application
  • Insulation damaged
  • Original refrigeration calculation incorrect

Signs of insufficient capacity

  • System reaches temperature when empty but not when loaded
  • Room performs overnight but not during working hours
  • Temperature rises significantly after deliveries
  • Compressor runs almost continuously
  • Performance worsens during summer
  • No obvious refrigerant, fan or control fault is found
  • Room never achieved the intended temperature reliably
  • Recovery takes much longer than the required period

How capacity should be checked

The refrigeration load should include:

  • Heat through walls, ceiling and floor
  • Warm air entering through the door
  • Product quantity
  • Product entry temperature
  • Required cooling time
  • People
  • Lighting
  • Evaporator fan motors
  • Defrost heat
  • Maximum ambient temperature

Room dimensions alone are not enough to select refrigeration capacity.

Other Possible Causes

The ten causes above are common, but they are not the only possibilities.

Additional faults may include:

  • Blocked filter drier
  • Restricted expansion valve
  • Incorrect superheat
  • Solenoid valve not opening fully
  • Liquid-line restriction
  • Faulty pressure control
  • Incorrect refrigerant charge
  • Refrigerant overcharge
  • Air or other non-condensables in the system
  • Evaporator fan rotating in the wrong direction
  • Three-phase compressor rotating incorrectly
  • Blocked drain
  • Incorrect pipe sizing
  • Excessive pipe-run length
  • Poor condenser location
  • Voltage problems
  • Intermittent electrical connections
  • Incorrect replacement components

High pressure, for example, may result from a dirty condenser, failed fan, refrigerant overcharge, non-condensables, restricted pipework or incorrect controls. Replacing components without measuring the system can therefore lead to an incorrect diagnosis.

Why a Cold Room Cools When Empty but Not When Loaded

This symptom often points to a load, airflow or capacity problem.

Possible causes include:

  • Excessive stock quantity
  • Products loaded warm
  • Stock blocking evaporator airflow
  • Inadequate refrigeration capacity
  • Door remaining open during loading
  • Too little recovery time
  • Products packed too tightly
  • Refrigerant charge marginal
  • Dirty condenser
  • Evaporator beginning to ice

The technician needs to know:

  • Quantity of product loaded
  • Product entry temperature
  • Time of loading
  • Required storage temperature
  • Expected pull-down time
  • Door-opening duration
  • Temperature before and after loading

A holding cold room designed for pre-chilled products may not have enough capacity to cool a large quantity of warm product rapidly.

Why the Compressor Runs Continuously but the Cold Room Is Not Cold

Continuous compressor operation means the controller continues requesting cooling or the system is not satisfying the control condition.

Possible causes include:

  • Dirty condenser
  • Low refrigerant charge
  • Refrigerant restriction
  • Evaporator icing
  • Failed evaporator fan
  • Damaged door seal
  • Open door
  • Excessive product load
  • Undersized refrigeration unit
  • Insulation failure
  • Compressor losing pumping capacity
  • Temperature sensor fault
  • Setpoint set too low

Do not assume that a continuously running compressor is automatically defective.

The technician should measure system pressures, temperatures, electrical current, airflow and control operation before reaching that conclusion.

Why the Temperature Rises During the Day

A room that cools correctly overnight but becomes too warm during business hours is often experiencing an excessive daytime load.

Possible factors include:

  • Frequent door openings
  • Warm deliveries
  • High kitchen or warehouse temperature
  • Direct sunlight on outdoor panels
  • Condenser exposed to hot recirculated air
  • Staff leaving the door open
  • More people entering the room
  • Increased product handling
  • Insufficient refrigeration capacity
  • Dirty condenser unable to cope with peak ambient heat

The operating pattern should be reviewed alongside the equipment.

Installing a larger compressor may not be the best solution where the main problem is an open door, blocked condenser or poor product-loading procedure.

Why Cold-Room Temperature Fluctuates

Temperature fluctuation can result from normal compressor cycling, but large or irregular swings may indicate:

  • Controller differential set too wide
  • Probe installed in the wrong position
  • Loose or faulty sensor
  • Door opened frequently
  • Defrost cycles incorrectly configured
  • Evaporator icing
  • Compressor short cycling
  • Refrigerant feed instability
  • Oversized equipment
  • Poor airflow
  • High product load
  • Intermittent fan operation

Record the temperature over time rather than relying on a single reading.

A temperature logger can help show whether the rise corresponds with:

  • Deliveries
  • Door openings
  • Defrost cycles
  • Hot periods of the day
  • Equipment shutdowns
  • Electrical interruptions

Safe Checks a Business Can Perform

Without opening the refrigeration system or electrical equipment, staff can check:

  • Whether the room has electrical power
  • Whether the controller is on
  • Whether an alarm code is displayed
  • Whether the setpoint was changed
  • Whether the door closes fully
  • Whether the gasket has visible damage
  • Whether stock blocks the evaporator
  • Whether evaporator fans appear to run
  • Whether the coil is visibly iced
  • Whether the condenser is obstructed
  • Whether the condenser fan appears to run
  • Whether a recent warm delivery explains a temporary rise
  • Whether an independent thermometer confirms the controller reading

Record:

  • Room temperature
  • Setpoint
  • Time the fault began
  • Alarm codes
  • Recent deliveries
  • Unusual sounds
  • Visible ice
  • Whether the compressor and fans are running

This information can shorten the diagnostic process.

What Should Not Be Attempted Without a Technician?

Do not attempt to:

  • Add refrigerant
  • Release refrigerant
  • Bypass pressure controls
  • Bypass overload protection
  • Replace a compressor
  • Change expansion-valve settings
  • Open live electrical panels
  • Force contactors closed
  • Melt ice using open flames
  • Break ice from a coil with sharp tools
  • Reset a repeatedly tripping breaker without investigation
  • Operate equipment with damaged electrical wiring

Refrigeration systems contain pressurised refrigerant and high-voltage electrical components. Incorrect work can cause injury, equipment damage, refrigerant loss or fire.

Information to Give the Refrigeration Technician

Provide:

  • Required room temperature
  • Current temperature
  • Product type
  • Product quantity
  • Product entry temperature
  • When the fault started
  • Whether the problem is constant or intermittent
  • Whether the compressor runs
  • Whether condenser and evaporator fans run
  • Alarm codes
  • Photographs of ice or damaged components
  • Previous repairs
  • Recent refrigerant additions
  • Whether equipment was relocated
  • Whether room size or usage changed
  • Whether the fault is worse during hot weather

The more accurate the operating history, the easier it is to distinguish a component failure from an application or capacity problem.

What a Professional Cold-Room Diagnostic Should Include

Depending on the fault, a technician may inspect:

  • Controller and sensor readings
  • Compressor operation
  • Electrical voltage and current
  • Contactors and overloads
  • Condenser cleanliness
  • Condenser fan operation
  • Evaporator airflow
  • Evaporator ice pattern
  • Defrost heaters and sensors
  • Refrigerant pressures
  • Superheat and subcooling where applicable
  • Leak points
  • Expansion device
  • Solenoid valves
  • Filter drier
  • Door seals
  • Panel joints
  • Drainage
  • Product load
  • Equipment capacity

A diagnosis should identify both the failed component and the reason it failed where possible.

When Is the Problem an Emergency?

Arrange urgent assistance when:

  • Product temperature is outside its safe range
  • The room temperature continues rising
  • Frozen products begin thawing
  • The compressor repeatedly trips
  • A breaker will not remain on
  • There is a burning smell
  • Refrigerant or oil is visibly escaping
  • Electrical wiring is damaged
  • Water reaches electrical equipment
  • The compressor is extremely hot or noisy
  • Ice prevents fans from rotating
  • A door cannot close
  • High-value or temperature-sensitive stock is at risk

Move stock to suitable backup refrigeration where this can be done safely and in accordance with the product’s handling requirements.

How Preventive Maintenance Reduces Cooling Problems

Many cold-room temperature failures develop gradually.

A maintenance programme should include:

  • Condenser cleaning
  • Evaporator inspection
  • Fan checks
  • Door-gasket inspection
  • Controller testing
  • Temperature-sensor verification
  • Defrost checks
  • Drain cleaning
  • Electrical connection inspection
  • Refrigerant leak checks
  • Operating-pressure assessment
  • Panel and door inspection

Heatcraft recommends regular cleaning of evaporator coils and fan blades and checking that drain pans remain clear of debris, obstruction and ice.

The correct service interval depends on the environment. A condenser near cooking grease, flour dust or production debris may need more frequent cleaning than one in a clean, ventilated plant room.

Frequently Asked Questions

Why is my cold room not reaching temperature?

Common causes include a dirty condenser, refrigerant leak, failed fan, iced evaporator, damaged door gasket, incorrect controller setting, compressor fault, poor airflow, insulation failure or undersized equipment.

Why is the cold room compressor running but not cooling?

The compressor may be operating while the system has low refrigerant, restricted refrigerant flow, poor heat rejection, an iced evaporator, failed fans or reduced compressor pumping capacity.

Can a dirty condenser stop a cold room from cooling?

Yes. Dirt restricts heat rejection, raises condensing pressure and reduces refrigeration performance. Severe blockage can also cause high-pressure shutdowns.

How do I know whether the cold room is low on refrigerant?

Possible signs include continuous compressor operation, reduced cooling, partial evaporator icing and oil stains near a leak. These signs are not conclusive, so pressures, temperatures and leak points must be checked by a technician.

Why is the evaporator covered in ice?

Possible causes include defrost failure, excessive moisture entering through the door, failed fans, incorrect controller settings, a blocked drain or refrigerant-feed problems.

Can I switch the cold room off to melt the ice?

Switching it off may melt the ice, but stock must first be protected and water must be managed safely. The underlying cause still needs to be diagnosed before normal operation resumes.

Why does the room cool overnight but not during the day?

Daytime door traffic, warm deliveries, high ambient temperature, blocked condenser airflow or insufficient refrigeration capacity may be increasing the load beyond what the system can handle.

Can a damaged door seal increase the room temperature?

Yes. Warm air entering through a damaged seal increases heat and moisture load, causing longer compressor operation and possible evaporator icing.

Why is the displayed temperature different from the product temperature?

The sensor measures temperature at one location. Poor airflow, recent loading, sensor position or calibration errors can cause the displayed air temperature to differ from product temperature.

Does continuous compressor operation mean the compressor is faulty?

Not necessarily. Continuous running can also result from dirty coils, low refrigerant, open doors, heavy product loads, insulation damage or an undersized system.

How often should a cold room be serviced?

The correct interval depends on usage and environmental conditions. High-use kitchens, food factories and dusty locations may require more frequent maintenance than clean, lightly used facilities.

Should refrigerant simply be added when cooling performance drops?

No. The system should first be tested for leakage and other faults. Repeated regassing without repairing the leak is not a permanent solution.

Restore the Cause, Not Only the Temperature

A cold room that is not reaching temperature is showing the result of a problem. The real cause may be in the condenser, evaporator, refrigerant circuit, controls, insulated enclosure or way the room is being used.

The most common causes are:

  1. Dirty condenser
  2. Refrigerant leak
  3. Failed condenser fan
  4. Iced evaporator
  5. Damaged door seal
  6. Incorrect controller setting
  7. Compressor problem
  8. Poor internal airflow
  9. Insulation failure
  10. Undersized refrigeration equipment

Avoid replacing components based on symptoms alone. Similar temperature problems can result from completely different faults, so the system should be tested under actual operating conditions.

Glotech Group provides commercial diagnostics, cold-room repairs, compressor replacements, fan repairs, leak detection, door-seal replacement and refrigeration maintenance. Visit the commercial cold-room repairs page to arrange an assessment.